Product · Whitespace

Data Room

2 level whitespace module

The data hall of an AI and HPC data center, factory-built for the densest hardware. IT on the ground floor, power and piping on the level above, delivered wired, piped and FAT-tested, ready to connect.

Render of an open Kontena data room module in a grey hall: racks below, cable trays and red cooling pipework on the level above
  • 2 levelsIT floor below, utilities above
  • 32 racksper hall in two rows, 230 kW nominal each
  • Up to 6 MWIT capacity per data hall
  • 5 monthsfrom engineering start to the first modules
Explore

Look inside the hall.

Pick a part of the hall to see what it does and where it sits.

  1. Two rows of racks face the outer aisles; the contained rear aisle carries only power and water.

  2. Grating walkways above the racks. Power and cooling are serviced here, away from the IT.

  3. A busway per row with plug-in tap-offs at every rack position, added or moved without a shutdown.

  4. A stainless steel loop to every rack: about 85% of the heat leaves through direct liquid cooling, ready for up to +300 kW per rack.

  5. Fibre and copper trays run on the utility level, straight above the rack rows.

  6. Power, water and fibre enter through feed-through plates and flanges on the end wall, ready to connect to the data center network infrastructure on site.

Cutaway render of a Kontena data room: racks on the ground floor, busways, tap-offs and cooling pipework on the utility level above
Two levels

Two levels, two jobs.

IT work and maintenance on power and cooling never get in each other's way.

Level 0

IT floor

Two rows of racks facing the outer aisles. The contained rear aisle between them carries only power and water, so the floor stays clear for people and hardware.

Level 1

Utility level

Grating walkways with busways, tap-off boxes, fibre trays and the headers of the liquid loop, the chilled water and the facility water. Power and cooling are serviced up here, above the IT and out of the way of the people working on it.

Render of the IT floor of a Kontena data room: an aisle between two rows of black racks, a door at the endRender of the utility level of a Kontena data room: a grating walkway between grey and red cooling pipes, valves and busways
Level 0: the IT floor, an aisle between the rows of racksLevel 1: the utility level, walkway between the piping and busways
Inside the hall

Everything a data room needs, built in.

Power

Busways from four sources, two at every rack position, with plug-in tap-offs and branch metering. Tap-offs are added or moved without a shutdown. UPS and switchgear sit in the E-Houses next door.

Cooling

Liquid first: around 85% of the heat leaves through direct liquid cooling at the chip, via in-row CDUs at the row ends and a stainless steel loop to every rack. Rear door heat exchangers on a separate loop take the rest. Built for future density, up to +300 kW per rack.

Fire safety

Aspirating smoke detection and inert gas suppression in every hall, inside a fire-rated steel envelope. No water near the hardware.

Security

Secured entrance doors, access control, CCTV and intrusion detection, linked to the security zones of the site.

Monitoring

BMS and power monitoring pre-wired in the factory, with leak detection and drip trays under the piping. Ready to connect to your DCIM.

Structure

Insulated steel modules with ESD flooring, engineered for seismic loads and for transport by road, built to European structural standards.

Specifications

Standard where possible.

Hall
18.0 x 8.4 m (59 ft 1 in x 27 ft 7 in), 8.0 m (26 ft 3 in) high, on two levels
Modules
12 factory-built steel modules per hall
Racks
32 positions per hall in two rows
IT capacity
4.8 to 6 MW per hall, set by rack count and density
Rack density
230 kW nominal, 300 kW provisioned per rack position
Power
busway from four sources, two per rack position, tap-offs with branch metering
Cooling
direct liquid cooling via in-row CDUs (about 85% of the heat), rear door heat exchangers for the rest
Floor
ESD flooring, 20 kN/m², up to 1,500 kg per rack
Fire
aspirating detection, inert gas suppression, fire-rated envelope
Monitoring
BMS, power monitoring and leak detection, pre-wired
Design
EN 50600 Availability Class 3; Tier III design on request
Testing
factory acceptance test before shipping, site acceptance test on site
Compact module
9.0 x 3.0 x 4.0 m (29 ft 6 in x 9 ft 10 in x 13 ft 1 in), road legal, 8 rack positions

Typical values for one data hall. Exact figures depend on the project.

Scale

From one hall to a campus.

Every Kontena data center is built from the same hall. Add halls, and they become a power block; repeat the block, and it becomes a campus.

  1. One data hall

    about 4.8 MW IT

    A complete data room: racks, busways, piping and safety systems in one factory-built hall.

    Edge single cluster
  2. One power block

    9.6 MW IT

    Two halls with five E-Houses and their own mechanical yard, linked by a corridor spine.

    Repeatable MDC block
  3. A campus

    40 MW and beyond

    Power blocks repeat side by side, built in parallel and brought live phase by phase.

    Full scale facility
FAQ

Questions about the data room

Is there a smaller version?

Yes. A compact module of 9.0 x 3.0 x 4.0 m holds 8 rack positions at about 100 kW each, 150 kW and above where needed. It travels by road without escort and has corner castings for sea freight.

Which racks and cooling hardware can go in?

Any. We are vendor-independent: you choose the racks, CDUs and rear doors, or we supply and integrate them in the factory.

Can the data room go inside an existing building?

Yes. The same halls are placed inside existing buildings as sealed, insulated rooms. See Indoor retrofit.

Is there an air-cooled version?

Yes. For lower densities the hall is fitted for air cooling only; the structure and the factory process stay the same.

How fast is it ready?

Well-defined projects can have the first modules ready five to six months after engineering starts. Exact timing depends on the project.

Can we add halls later?

Yes. New halls connect to the corridor spine beside the running ones, without interrupting operation.

Get in touch

Tell us your load, your site and your timeline.

We come back with a first configuration and a schedule.