Product · Power

E-House

Power distribution

Switchgear, UPS and distribution in one factory-built steel module. Every E-House is wired and tested in our halls, then set beside the data hall and connected with short, prefabricated busways and cables.

Render of a Kontena E-House power module in an empty hall, a technician walking pastRender of a battery room inside an E-House: a row of lithium battery cabinets, fire suppression nozzles and piping overhead
The E-House, wired and tested in our hallsExample: the battery room, its own fire-rated compartment with suppression
  • 3 MWper E-House in our reference blocks
  • 2 levelsstackable, to keep the plot small
  • 5 to 10 minbattery autonomy on lithium iron phosphate
  • 4M3or N+1 and 2N, to match your availability target
What it does

Built in our halls, ready to connect.

Switchgear

Low voltage main switchboards with a utility and a standby incomer, and a paralleling section for two generator sets.

UPS and batteries

Modular double conversion UPS with lithium iron phosphate batteries for 5 to 10 minutes, in a separate, fire-rated compartment.

Four power lines

In a 4M3 layout four E-Houses each feed one line, and any three of them carry the full critical load.

Distribution

UPS output, mechanical and auxiliary boards, with busway connections that run straight into the data hall.

Climate

Its own CRAH cooling and ventilation, so the electrical equipment stays in its comfort zone in every season.

Safety

Arc flash rated layout, fire detection and clean agent or aerosol suppression, access control and clear service aisles.

Monitoring

BMS and power monitoring points and the network switch for the controls, all pre-wired in the factory.

Europe and North America

IEC and EN versions for Europe, UL listed switchboards and UPS for North America, at 50 or 60 Hz.

Without diesel

For inference loads the batteries can bridge grid events and close down cleanly, without a generator on site.

Specifications

Typical specifications.

Function
low voltage power distribution per power line
Rating
about 3 MW per E-House in our reference blocks; sized per project
Content
switchgear, UPS, batteries, distribution, auxiliaries
Redundancy
4M3 (four lines, any three carry the load), N+1 or 2N
UPS
modular, double conversion, lithium iron phosphate batteries for 5 to 10 minutes
Standby
utility and standby incomers, paralleling for two generator sets
Placement
beside the data hall, single or stacked on two levels
Enclosure
insulated steel module, transport by road
Testing
factory acceptance test including load and protection tests
Standards
IEC and EN; UL 891 and UL 1778 for North America; 50 or 60 Hz

Typical values. Exact figures depend on the project.

FAQ

Questions about the E-House

Which brands do you use?

We are vendor-independent. We build with the switchgear and UPS brands you prefer, or propose a proven set.

Is the transformer inside the E-House?

It can be. Smaller ratings fit in the module; larger ones stand on their own pad next to it.

Can an E-House be added later?

Yes. Each power path has its own E-House, so a new one connects without touching the paths already running.

Can you add UPS protection to an existing data center?

Yes. A retrofit E-House brings a UPS skid and a separate battery module, built as its own fire cell, next to halls that run without UPS today. Nothing is placed inside the halls and the existing busbars stay as they are.

Do we need diesel generators?

Not always. For inference loads, lithium batteries can ride through grid events and finish what is running. Where standby power is needed, the E-House is ready for generator sets.

Get in touch

Tell us your load, your site and your timeline.

We come back with a first configuration and a schedule.